

Mon - Sat 9:00 - 17:30
Foam-based fire suppression remains one of the most effective methods to control flammable liquid fires in refineries, chemical plants, tank farms, aircraft hangars, and process industries. The correct foam application rate and application time are critical for the successful extinguishment of liquid fuel fires. International and national standards like NFPA 11 (US), EN 13565 (Europe), Lastfire (Oil Industry Consortium), and OISD (India) provide guidance for foam system design.
Foam Application Rate is defined as the quantity of finished foam solution (water + foam concentrate + air) applied per unit area of the fuel surface, usually expressed in liters per minute per square meter (L/min/m²) or gallons per minute per square foot (gpm/ft²).
It represents the minimum foam flow rate needed to:
Control and extinguish the fire,
Overcome fuel vaporization and radiant heat,
Provide safety against foam destruction or burn-back.
Foam application rate depends on:
Fuel Type: Hydrocarbons vs polar solvents.
Hazard Scenario: Tank full surface fire, rim seal fire, bund spill, pool fire, or hangar fire.
Foam Type: AFFF, AR-AFFF, FFFP, or High Expansion.
Testing Performance: Fire test pans, extinguishment time, burn-back resistance, drainage time.
Applicable Standard: NFPA 11, EN 13565, Lastfire, OISD, etc.
Pan Fire Tests (NFPA 11, EN 1568, OISD 116): Foam applied on heptane/diesel pool fires.
Control & Extinguishment Time Measurement.
Burn-back Resistance: Foam disturbed and relit to check endurance.
Drainage Time Test: Stability of foam blanket measured.
Fuels used in testing:
Heptane/Iso-octane – hydrocarbon representation.
Diesel/Kerosene – medium volatility.
Isopropanol/Ethanol – for AR foams.
Aviation Fuel (Jet A1) – aircraft fire tests.
Fixed Roof Tank (Full Surface Fire): 4.1 L/min/m², 65 min
Floating Roof Tank (Rim Seal): 12.2 L/min/m², 55 min
Aircraft Hangars: 6.5–10.2 L/min/m², 10 min
Tank Protection: 4.0–6.0 L/min/m², ≥30 min
Bund Area (Spill Fire): 6.5–10.0 L/min/m², 20–30 min
Cone Roof Tank (Full Surface Fire): 6.5 L/min/m², 65 min
Floating Roof Tank (Rim Seal): 12.2 L/min/m², 55 min
(As per OISD-117 and OISD-STD-244, for petroleum storage installations):
Fixed Roof Tank (Full Surface Fire): 5.0 L/min/m², minimum 65 min
Floating Roof Tank (Rim Seal Fire): 12.0 L/min/m², minimum 55 min
Bund Area (Spill Fire): 6.5 L/min/m², minimum 30 min
Pool Fire (Hydrocarbon Spills): 6.5–10 L/min/m² depending on hazard, ≥30 min
A pool fire occurs when liquid fuel spills and ignites, forming a fire across a confined or unconfined surface.
NFPA & EN: Typically recommend 6.5–10 L/min/m².
OISD: Minimum 6.5 L/min/m² for hydrocarbon pool fires, with application time ≥30 min.
For polar solvents: Higher rates are needed and alcohol-resistant foams (AR-AFFF) must be used.
Tank Diameter: 20 m
Surface Area = π × (20/2)² = 314 m²
Foam Application Rate = 4.1 L/min/m²
Foam Flow Rate = 1,287 L/min
Application Time = 65 min
Total Foam Solution = 83,655 L
Foam Concentrate (3%): 2,509 L
Bund Area: 400 m²
Foam Application Rate = 6.5 L/min/m²
Foam Flow Rate = 2,600 L/min
Application Time = 30 min
Total Foam Solution = 78,000 L
Foam Concentrate (6%): 4,680 L
Pool Fire Area: 100 m²
Application Rate = 6.5 L/min/m²
Foam Flow Rate = 650 L/min
Application Time = 30 min
Total Foam Solution = 19,500 L
Foam Concentrate (3%): 585 L
Wind Losses:
For outdoor fires, foam streams are affected by wind.
Recommended design margin: 10–15% extra foam solution.
Obstructions:
Tank appurtenances, dikes, and structures may shadow foam distribution.
Foam Quality:
Expansion ratio, drainage time, and burn-back resistance must be tested.
Redundancy:
Backup foam tanks, fire water pumps, and alternate discharge devices should be included.
Correct foam application rate and application time are the backbone of foam fire suppression design. NFPA, EN, Lastfire, and OISD provide detailed requirements, with OISD being mandatory in India for petroleum facilities. Pool fires, tank fires, and bund fires all demand different rates, but a safety margin (wind, redundancy, foam quality) must always be included.
π For design, installation, consulting, and commissioning of foam-based and other fire protection systems, contact us:
π§ agnirakshaniti@gmail.com